|
||||||
|---|---|---|---|---|---|---|
| Home | 29 CFR | 40 CFR | 49 CFR | Federal Register | MSDS Search | Purchase CFR e-Books |
§141.135 Treatment technique for control of disinfection byproduct (DBP) precursors.
(a) Applicability. (1) Subpart H systems using conventional filtration treatment (as defined in §141.2 ) must operate with enhanced coagulation or enhanced softening to achieve the TOC percent removal levels specified in paragraph (b) of this section unless the system meets at least one of the alternative compliance criteria listed in paragraph (a)(2) or (a)(3) of this section.
(2) Alternative compliance criteria for enhanced coagulation and enhanced softening systems. Subpart H systems using conventional filtration treatment may use the alternative compliance criteria in paragraphs (a)(2)(i) through (vi) of this section to comply with this section in lieu of complying with paragraph (b) of this section. Systems must still comply with monitoring requirements in §141.132(d).
(i) The system's source water TOC level, measured according to §141.131(d)(3), is less than 2.0 mg/L, calculated quarterly as a running annual average.
(ii) The system's treated water TOC level, measured according to §141.131(d)(3), is less than 2.0 mg/L, calculated quarterly as a running annual average.
(iii) The system's source water TOC level, measured according to
§141.131(d)(3), is less than 4.0 mg/L, calculated quarterly as a running annual
average; the source water alkalinity, measured according to §141.131(d)(1), is
greater than 60 mg/L (as CaCO (iv) The TTHM and HAA5 running annual averages are no greater than 0.040 mg/L
and 0.030 mg/L, respectively, and the system uses only chlorine for primary
disinfection and maintenance of a residual in the distribution system.
(v) The system's source water SUVA, prior to any treatment and measured
monthly according to §141.131(d)(4), is less than or equal to 2.0 L/mg-m,
calculated quarterly as a running annual average.
(vi) The system's finished water SUVA, measured monthly according to
§141.131(d)(4), is less than or equal to 2.0 L/mg-m, calculated quarterly as a
running annual average.
(3) Additional alternative compliance criteria for softening systems.
Systems practicing enhanced softening that cannot achieve the TOC removals
required by paragraph (b)(2) of this section may use the alternative compliance
criteria in paragraphs (a)(3)(i) and (ii) of this section in lieu of complying
with paragraph (b) of this section. Systems must still comply with monitoring
requirements in §141.132(d).
(i) Softening that results in lowering the treated water alkalinity to less
than 60 mg/L (as CaCO (ii) Softening that results in removing at least 10 mg/L of magnesium
hardness (as CaCO (b) Enhanced coagulation and enhanced softening performance
requirements. (1) Systems must achieve the percent reduction of TOC
specified in paragraph (b)(2) of this section between the source water and the
combined filter effluent, unless the State approves a system's request for
alternate minimum TOC removal (Step 2) requirements under paragraph (b)(3) of
this section.
(2) Required Step 1 TOC reductions, indicated in the following table, are
based upon specified source water parameters measured in accordance with
§141.131(d). Systems practicing softening are required to meet the Step 1 TOC
reductions in the far-right column (Source water alkalinity >120 mg/L) for
the specified source water TOC: (3) Subpart H conventional treatment systems that cannot achieve the Step 1
TOC removals required by paragraph (b)(2) of this section due to water quality
parameters or operational constraints must apply to the State, within three
months of failure to achieve the TOC removals required by paragraph (b)(2) of
this section, for approval of alternative minimum TOC (Step 2) removal
requirements submitted by the system. If the State approves the alternative
minimum TOC removal (Step 2) requirements, the State may make those requirements
retroactive for the purposes of determining compliance. Until the State approves
the alternate minimum TOC removal (Step 2) requirements, the system must meet
the Step 1 TOC removals contained in paragraph (b)(2) of this section.
(4) Alternate minimum TOC removal (Step 2) requirements. Applications
made to the State by enhanced coagulation systems for approval of alternate
minimum TOC removal (Step 2) requirements under paragraph (b)(3) of this section
must include, at a minimum, results of bench- or pilot-scale testing conducted
under paragraph (b)(4)(i) of this section. The submitted bench- or pilot-scale
testing must be used to determine the alternate enhanced coagulation level.
(i) Alternate enhanced coagulation level is defined as coagulation at
a coagulant dose and pH as determined by the method described in paragraphs
(b)(4)(i) through (v) of this section such that an incremental addition of 10
mg/L of alum (or equivalent amount of ferric salt) results in a TOC removal of ≤
0.3 mg/L. The percent removal of TOC at this point on the "TOC removal versus
coagulant dose" curve is then defined as the minimum TOC removal required for
the system. Once approved by the State, this minimum requirement supersedes the
minimum TOC removal required by the table in paragraph (b)(2) of this section.
This requirement will be effective until such time as the State approves a new
value based on the results of a new bench- and pilot-scale test. Failure to
achieve State-set alternative minimum TOC removal levels is a violation of
National Primary Drinking Water Regulations.
(ii) Bench- or pilot-scale testing of enhanced coagulation must be conducted
by using representative water samples and adding 10 mg/L increments of alum (or
equivalent amounts of ferric salt) until the pH is reduced to a level less than
or equal to the enhanced coagulation Step 2 target pH shown in the following
table: (iii) For waters with alkalinities of less than 60 mg/L for which addition of
small amounts of alum or equivalent addition of iron coagulant drives the pH
below 5.5 before significant TOC removal occurs, the system must add necessary
chemicals to maintain the pH between 5.3 and 5.7 in samples until the TOC
removal of 0.3 mg/L per 10 mg/L alum added (or equivalant addition of iron
coagulant) is reached.
(iv) The system may operate at any coagulant dose or pH necessary (consistent
with other NPDWRs) to achieve the minimum TOC percent removal approved under
paragraph (b)(3) of this section.
(v) If the TOC removal is consistently less than 0.3 mg/L of TOC per 10 mg/L
of incremental alum dose at all dosages of alum (or equivalant addition of iron
coagulant), the water is deemed to contain TOC not amenable to enhanced
coagulation. The system may then apply to the State for a waiver of enhanced
coagulation requirements.
(c) Compliance calculations. (1) Subpart H systems other than those
identified in paragraph (a)(2) or (a)(3) of this section must comply with
requirements contained in paragraph (b)(2) or (b)(3) of this section. Systems
must calculate compliance quarterly, beginning after the system has collected 12
months of data, by determining an annual average using the following method:
(i) Determine actual monthly TOC percent removal, equal to: (ii) Determine the required monthly TOC percent removal (from either the
table in paragraph (b)(2) of this section or from paragraph (b)(3) of this
section).
(iii) Divide the value in paragraph (c)(1)(i) of this section by the value in
paragraph (c)(1)(ii) of this section.
(iv) Add together the results of paragraph (c)(1)(iii) of this section for
the last 12 months and divide by 12.
(v) If the value calculated in paragraph (c)(1)(iv) of this section is less
than 1.00, the system is not in compliance with the TOC percent removal
requirements.
(2) Systems may use the provisions in paragraphs (c)(2)(i) through (v) of
this section in lieu of the calculations in paragraph (c)(1)(i) through (v) of
this section to determine compliance with TOC percent removal requirements.
(i) In any month that the system's treated or source water TOC level,
measured according to §141.131(d)(3), is less than 2.0 mg/L, the system may
assign a monthly value of 1.0 (in lieu of the value calculated in paragraph
(c)(1)(iii) of this section) when calculating compliance under the provisions of
paragraph (c)(1) of this section.
(ii) In any month that a system practicing softening removes at least 10 mg/L
of magnesium hardness (as CaCO (iii) In any month that the system's source water SUVA, prior to any
treatment and measured according to §141.131(d)(4), is ≤2.0 L/mg-m, the system
may assign a monthly value of 1.0 (in lieu of the value calculated in paragraph
(c)(1)(iii) of this section) when calculating compliance under the provisions of
paragraph (c)(1) of this section.
(iv) In any month that the system's finished water SUVA, measured according
to §141.131(d)(4), is ≤2.0 L/mg-m, the system may assign a monthly value of 1.0
(in lieu of the value calculated in paragraph (c)(1)(iii) of this section) when
calculating compliance under the provisions of paragraph (c)(1) of this section.
(v) In any month that a system practicing enhanced softening lowers
alkalinity below 60 mg/L (as CaCO (3) Subpart H systems using conventional treatment may also comply with the
requirements of this section by meeting the criteria in paragraph (a)(2) or (3)
of this section.
(d) Treatment technique requirements for DBP precursors. The
Administrator identifies the following as treatment techniques to control the
level of disinfection byproduct precursors in drinking water treatment and
distribution systems: For Subpart H systems using conventional treatment,
enhanced coagulation or enhanced softening.
[63 FR 69466, Dec. 16, 1998, as amended at 66 FR 3779, Jan. 16,
2001] Step 1 Required Removal of TOC by Enhanced Coagulation and Enhanced
Softening for Subpart H Systems Using Conventional Treatment [SU]1 2[/
SU]
------------------------------------------------------------------------
Source-water alkalinity, mg/L as CaCO
[INF]3[/INF] (in precentages)
Source-water TOC, mg/L -----------------------------------------
>120
0-60 >60-120 [SU]3[/SU]
------------------------------------------------------------------------
>2.0-4.0................... 35.0 25.0 15.0
>4.0-8.0................... 45.0 35.0 25.0
>8.0....................... 50.0 40.0 30.0
------------------------------------------------------------------------
\1\ Systems meeting at least one of the conditions in paragraph
(a)(2)(i)-(vi) of this section are not required to operate with
enhanced coagulation.
\2\ Softening system meeting one of the alternative compliance criteria
in paragraph (a)(3) of this section are not required to operate with
enhanced softening.
\3\ System practicing softening must meet the TOC removal requirements
in this column.
Enhanced Coagulation Step 2 target pH
------------------------------------------------------------------------
Alkalinity (mg/L as CaCO[INF]3[/INF]) Target pH
------------------------------------------------------------------------
0-60....................................................... 5.5
>60-120................................................. 6.3
>120-240................................................ 7.0
>240.................................................... 7.5
------------------------------------------------------------------------