| General
requirements |
An employer must:
- Provide portable fire extinguishers and mount,
locate, and identify them so that they are readily
accessible to employees without subjecting the
employees to possible injury. 1910.157(c)(1)
- Use only approved portable fire extinguishers.
1910.157(c)(2)
- Not use portable fire extinguishers that use
carbon tetrachloride or chlorobromomethane extinguishing
agents. 1910.157(c)(3)
- Assure that portable fire extinguishers are
maintained, fully charged, operating properly,
and kept in designated places at all times except
during use. 1910.157(c)(4)
- Remove from service all soldered or riveted
shell self-generating soda acid or self-generating
foam or gas cartridge water type portable fire
extinguishers that are operated by inverting
the extinguisher to rupture the cartridge or
to initiate an uncontrollable pressure generating
chemical reaction to expel the agent. 1910.157(c)(5)
|
| Selection
and distribution |
An employer must:
- Provide portable fire extinguishers for employee
use and select and distribute the extinguishers
based on the types of anticipated workplace
fires and on the size and degree of hazard that
would affect their use. 1910.157(d)(1)
- Ensure that the travel distance for employees
to any Class A extinguisher is 75 feet (22.9
meters) or less. 1910.157(d)(2)
- The employer may use
uniformly spaced standpipe systems or hose stations
connected to a sprinkler system installed for
emergency use by employees instead of Class
A portable fire extinguishers, provided that
such systems meet the respective requirements
of
1910.158 or 1910.159,
that they provide total coverage of the area
to be protected, and that employees are trained
at least annually in their use. 1910.157(d)(3)
- Ensure that the travel distance for employees
to any Class B extinguisher is 50 feet (15.2
meters) or less. 1910.157(d)(4)
- Base the travel distance for employees to
any Class C extinguisher on the pattern for
the existing Class A or Class B extinguishers.
1910.157(d)(5)
- Ensure that the travel distance for employees
from the combustible metal working area to any
Class D extinguisher is 75 feet (22.9 meters)
or less. Portable fire extinguishers for Class
D hazards are required in areas where combustible
metal powders, flakes, shavings, or similarly
sized products are generated at least once every
two weeks. 1910.157(d)(6)
|
| Inspection,
maintenance, and testing |
An employer must:
- Inspect, maintain, and test all portable fire
extinguishers in the workplace. 1910.157(e)(1)
- Visually inspect portable extinguishers or
hoses monthly. 1910.157(e)(2)
- Perform an annual maintenance check on portable
fire extinguishers. Stored pressure extinguishers
do not require an internal examination. The
employer must record the annual maintenance
date and retain this record for one year after
the last entry or the life of the shell, whichever
is less. The record must be made available to
the Assistant Secretary upon request. 1910.157(e)(3)
- Empty and maintain dry chemical extinguishers
(that require a 12-year hydrostatic test) every
six years. Dry chemical extinguishers that have
non-refillable disposable containers are exempt
from this requirement. When recharging or hydrostatic
testing is performed, the six-year requirement
begins from that date. 1910.157(e)(4)
- Provide alternate equivalent protection when
portable fire extinguishers are removed from
service for maintenance and recharging. 1910.157(e)(5)
|
| Hydrostatic
testing |
An employer must:
- Assure that hydrostatic testing is performed
by trained persons with suitable testing equipment
and facilities. 1910.157(f)(1)
- Assure that portable extinguishers are hydrostatically
tested at the intervals listed in
Table L-1 of this section, except under
any of the following conditions: 1910.157(f)(2)
- Assure that an internal examination of cylinders
and shells to be tested is made before the hydrostatic
tests. 1910.157(f)(3)
|
Table L-1 |
| Type
of extinguishers |
Test
interval
(years) |
|
Soda acid (soldered brass shells) (until 1/1/82) |
5 |
|
Soda acid (stainless steel shell) |
5 |
|
Cartridge operated water and/or antifreeze |
5 |
| Stored
pressure water and/or antifreeze |
5 |
| Wetting
agent |
5 |
| Foam
(soldered brass shells) (until 1/1/82) |
5 |
| Foam
(stainless steel shell) |
5 |
| Aqueous
Film Forming foam (AFFF) |
5 |
| Loaded
stream |
5 |
| Dry
chemical with stainless steel |
5 |
| Carbon
Dioxide |
5 |
| Dry
chemical, stored pressure, with mild steel,
brazed brass or aluminum shells |
12 |
Dry
chemical, cartridge or cylinder operated,
with
mild steel shells |
12 |
| Halon
1211 |
12 |
| Halon
1301 |
12 |
Dry
powder, cartridge or cylinder operated with
mild
steel shells |
12 |
| *Footnote:
Extinguishers having shells constructed of
copper or brass joined by soft solder or rivets
shall not be hydrostatically tested and shall
be removed from service by January 1, 1982.
(Not permitted) |
- Assure that portable fire extinguishers are
hydrostatically tested whenever they show new
evidence of corrosion or mechanical injury,
except under the conditions listed in paragraphs
(f)(2)(i)-(v)
of this section. 1910.157(f)(4)
- Assure that hydrostatic tests are performed
on extinguisher hose assemblies that are equipped
with a shut-off nozzle at the discharge end
of the hose. The test interval must be the same
as specified for the extinguisher. 1910.157(f)(5)
- Hydrostatically test carbon dioxide hose assemblies
with a shut-off nozzle at 1,250 psi (8,620 kPa).
1910.157(f)(6)
- Hydrostatically test dry chemical and dry
powder hose assemblies with a shut-off nozzle
at 300 psi (2,070 kPa). 1910.157(f)(7)
Hose assemblies passing a hydrostatic test do
not require any type of recording or stamping.
1910.157(f)(8)
- Test hose assemblies for carbon dioxide extinguishers
within a protective cage device. 1910.157(f)(9)
- Test carbon dioxide extinguishers and nitrogen
or carbon dioxide cylinders used with wheeled
extinguishers every five years at 5/3 of the
service pressure as stamped into the cylinder.
Nitrogen cylinders that comply with 49 CFR 173.34(e)(15)
may be hydrostatically tested every 10 years.
1910.157(f)(10)
- Hydrostatically test stored pressure and Halon
1211 types of extinguishers at the factory test
pressure, not to exceed two times the service
pressure. 1910.157(f)(11)
- Test self-generating type soda acid and foam
extinguishers at 350 psi (2,410 kPa). 1910.157(f)(12)
- Not use air or gas pressure for hydrostatic
testing. 1910.157(f)(13)
- Remove extinguisher shells, cylinders, or
cartridges that fail a hydrostatic pressure
test, or that are not fit for testing. 1910.157(f)(14)
- Ensure that the equipment for testing compressed
gas type cylinders be of the water jacket type.
The equipment must have an expansion indicator
that operates with an accuracy within 1 percent
of the total expansion or .1cc (.1mL) of liquid.
1910.157(f)(15)(i)
- Ensure that the equipment for testing non-compressed
gas type cylinders includes the following: 1910.157(f)(15)(ii)
- A hydrostatic test pump, hand or power operated,
capable of producing at least 150 percent
of the test pressure, which must include appropriate
check valves and fittings; 1910.157(f)(15)(ii)(A)
- A flexible connection for attachment to
fittings to test through the extinguisher
nozzle, test bonnet, or hose outlet, as is
applicable; and 1910.157(f)(15)(ii)(B)
- A protective cage or barrier for personal
protection of the tester, designed to provide
visual observation of the extinguisher under
test. 1910.157(f)(15)(ii)(C)
- Maintain and provide upon request to the
Assistant Secretary evidence that the required
hydrostatic testing of fire extinguishers has
been performed at the time intervals shown in
Table
L-1. Such evidence must be in the form of
a certification record that includes:
- The date of the test;
- The signature of the person who performed
the test; and
- The serial number, or other identifier,
of the fire extinguisher that was tested.
Such records must be kept until the extinguisher
is hydrostatically retested at the time interval
specified in
Table L-1 or until the extinguisher is taken
out of service, whichever comes first. 1910.157(f)(16)
|
| Training
and education |
An employer must:
- Provide an educational
program to familiarize employees with the general
principles of fire extinguisher use and the
hazards involved with incipient stage fire fighting.
1910.157(g)(1)
Provide this education when employees are first
hired and once a year thereafter. 1910.157(g)(2)
- Train employees (who have
been designated to use fire fighting equipment)
in the use of the equipment. 1910.157(g)(3)
Provide this training when employees are first
given this assignment and once a year thereafter.
.157(g)(4)
|
|
|