|
||||||||||||
|
|
|
|
|
|
||||||||
|
|
29 CFR | | 40 CFR |
| 49 CFR |
| FR Daily |
| MSDS |
|Seton |
§ 1910.399 Definitions applicable to this subpart.
Acceptable. An installation or equipment is acceptable to the Assistant Secretary of Labor, and approved within the meaning of this Subpart S:
(i) If it is accepted, or certified, or listed, or labeled, or otherwise determined to be safe by a nationally recognized testing laboratory; or
(ii) With respect to an installation or equipment of a kind which no nationally recognized testing laboratory accepts, certifies, lists, labels, or determines to be safe, if it is inspected or tested by another Federal agency, or by a State, municipal, or other local authority responsible for enforcing occupational safety provisions of the National Electrical Code and found in compliance with the provisions of the National Electrical Code as applied in this subpart; or
(iii) With respect to custom-made equipment or related installations which are designed, fabricated for, and intended for use by a particular customer, if it is determined to be safe for its intended use by its manufacturer on the basis of test data which the employer keeps and makes available for inspection to the Assistant Secretary and his authorized representatives. Refer to § 1910.7 for definition of nationally recognized testing laboratory.
Accepted. An installation is "accepted" if it has been inspected and found by a nationally recognized testing laboratory to conform to specified plans or to procedures of applicable codes.
Accessible. (As applied to wiring methods.) Capable of being removed or exposed without damaging the building structure or finish, or not permanently closed in by the structure or finish of the building. (See "concealed" and "exposed.")
Accessible. (As applied to equipment.) Admitting close approach; not guarded by locked doors, elevation, or other effective means. (See "Readily accessible.")
Ampacity. Current-carrying capacity of electric conductors expressed in amperes.
Appliances. Utilization equipment, generally other than industrial, normally built in standardized sizes or types, which is installed or connected as a unit to perform one or more functions such as clothes washing, air conditioning, food mixing, deep frying, etc.
Approved. Acceptable to the authority enforcing this subpart. The authority enforcing this subpart is the Assistant Secretary of Labor for Occupational Safety and Health. The definition of "acceptable" indicates what is acceptable to the Assistant Secretary of Labor, and therefore approved within the meaning of this Subpart.
Approved for the purpose. Approved for a specific purpose, environment, or application described in a particular standard requirement.
Suitability of equipment or materials for a specific purpose, environment or application may be determined by a nationally recognized testing laboratory, inspection agency or other organization concerned with product evaluation as part of its listing and labeling program. (See "Labeled" or "Listed.")
Armored cable. Type AC armored cable is a fabricated assembly of insulated conductors in a flexible metallic enclosure.
Askarel. A generic term for a group of nonflammable synthetic chlorinated hydrocarbons used as electrical insulating media. Askarels of various compositional types are used. Under arcing conditions the gases produced, while consisting predominantly of noncombustible hydrogen chloride, can include varying amounts of combustible gases depending upon the askarel type.
Attachment plug (Plug cap) (Cap). A device which, by insertion in a receptacle, establishes connection between the conductors of the attached flexible cord and the conductors connected permanently to the receptacle.
Automatic. Self-acting, operating by its own mechanism when actuated by some impersonal influence, as, for example, a change in current strength, pressure, temperature, or mechanical configuration.
Bare conductor. See "Conductor."
Bonding. The permanent joining of metallic parts to form an electrically conductive path which will assure electrical continuity and the capacity to conduct safely any current likely to be imposed.
Bonding jumper. A reliable conductor to assure the required electrical conductivity between metal parts required to be electrically connected.
Branch circuit. The circuit conductors between the final overcurrent device protecting the circuit and the outlet(s).
Building. A structure which stands alone or which is cut off from adjoining structures by fire walls with all openings therein protected by approved fire doors.
Cabinet. An enclosure designed either for surface or flush mounting, and provided with a frame, mat, or trim in which a swinging door or doors are or may be hung.
Cable tray system. A cable tray system is a unit or assembly of units or sections, and associated fittings, made of metal or other noncombustible materials forming a rigid structural system used to support cables. Cable tray systems include ladders, troughs, channels, solid bottom trays, and other similar structures.
Cablebus. Cablebus is an approved assembly of insulated conductors with fittings and conductor terminations in a completely enclosed, ventilated, protective metal housing.
Center pivot irrigation machine. A center pivot irrigation machine is a multi-motored irrigation machine which revolves around a central pivot and employs alignment switches or similar devices to control individual motors.
Certified. Equipment is "certified" if it (a) has been tested and found by a nationally recognized testing laboratory to meet nationally recognized standards or to be safe for use in a specified manner, or (b) is of a kind whose production is periodically inspected by a nationally recognized testing laboratory, and (c) it bears a label, tag, or other record of certification.
Circuit breaker. (i) (600 volts nominal, or less). A device designed to open and close a circuit by nonautomatic means and to open the circuit automatically on a predetermined overcurrent without injury to itself when properly applied within its rating.
(ii) (Over 600 volts, nominal). A switching device capable of making, carrying, and breaking currents under normal circuit conditions, and also making, carrying for a specified time, and breaking currents under specified abnormal circuit conditions, such as those of short circuit.
Class I locations. Class I locations are those in which flammable gases or vapors are or may be present in the air in quantities sufficient to produce explosive or ignitible mixtures. Class I locations include the following:
(i) Class I, Division 1. A Class I, Division 1 location is a location:
(a) in which hazardous concentrations of flammable gases or vapors may
exist under normal operating conditions; or (b) in which hazardous
concentrations of such gases or vapors may exist frequently because of repair or
maintenance operations or because of leakage; or (c) in which breakdown
or faulty operation of equipment or processes might release hazardous
concentrations of flammable gases or vapors, and might also cause simultaneous
failure of electric equipment. Note: This classification usually includes locations where volatile
flammable liquids or liquefied flammable gases are transferred from one
container to another; interiors of spray booths and areas in the vicinity of
spraying and painting operations where volatile flammable solvents are used;
locations containing open tanks or vats of volatile flammable liquids; drying
rooms or compartments for the evaporation of flammable solvents; locations
containing fat and oil extraction equipment using volatile flammable solvents;
portions of cleaning and dyeing plants where flammable liquids are used; gas
generator rooms and other portions of gas manufacturing plants where flammable
gas may escape; inadequately ventilated pump rooms for flammable gas or for
volatile flammable liquids; the interiors of refrigerators and freezers in which
volatile flammable materials are stored in open, lightly stoppered, or easily
ruptured containers; and all other locations where ignitible concentrations of
flammable vapors or gases are likely to occur in the course of normal
operations.
(ii) Class I, Division 2. A Class I, Division 2 location is a
location: (a) in which volatile flammable liquids or flammable gases are
handled, processed, or used, but in which the hazardous liquids, vapors, or
gases will normally be confined within closed containers or closed systems from
which they can escape only in case of accidental rupture or breakdown of such
containers or systems, or in case of abnormal operation of equipment; or
(b) in which hazardous concentrations of gases or vapors are normally
prevented by positive mechanical ventilation, and which might become hazardous
through failure or abnormal operations of the ventilating equipment; or
(c) that is adjacent to a Class I, Division 1 location, and to which
hazardous concentrations of gases or vapors might occasionally be communicated
unless such communication is prevented by adequate positive-pressure ventilation
from a source of clean air, and effective safeguards against ventilation failure
are provided. Note: This classification usually includes locations where volatile
flammable liquids or flammable gases or vapors are used, but which would become
hazardous only in case of an accident or of some unusual operating condition.
The quantity of flammable material that might escape in case of accident, the
adequacy of ventilating equipment, the total area involved, and the record of
the industry or business with respect to explosions or fires are all factors
that merit consideration in determining the classification and extent of each
location.
Piping without valves, checks, meters, and similar devices would not
ordinarily introduce a hazardous condition even though used for flammable
liquids or gases. Locations used for the storage of flammable liquids or a
liquefied or compressed gases in sealed containers would not normally be
considered hazardous unless also subject to other hazardous conditions.
Electrical conduits and their associated enclosures separated from process
fluids by a single seal or barrier are classed as a Division 2 location if the
outside of the conduit and enclosures is a nonhazardous location.
Class II locations. Class II locations are those that are hazardous
because of the presence of combustible dust. Class II locations include the
following:
(i) Class II, Division 1. A Class II, Division 1 location is a
location: (a) In which combustible dust is or may be in suspension in the
air under normal operating conditions, in quantities sufficient to produce
explosive or ignitible mixtures; or (b) where mechanical failure or
abnormal operation of machinery or equipment might cause such explosive or
ignitible mixtures to be produced, and might also provide a source of ignition
through simultaneous failure of electric equipment, operation of protection
devices, or from other causes, or (c) in which combustible dusts of an
electrically conductive nature may be present. Note: This classification may include areas of grain handling and
processing plants, starch plants, sugar-pulverizing plants, malting plants,
hay-grinding plants, coal pulverizing plants, areas where metal dusts and
powders are produced or processed, and other similar locations which contain
dust producing machinery and equipment (except where the equipment is dust-tight
or vented to the outside). These areas would have combustible dust in the air,
under normal operating conditions, in quantities sufficient to produce explosive
or ignitible mixtures. Combustible dusts which are electrically nonconductive
include dusts produced in the handling and processing of grain and grain
products, pulverized sugar and cocoa, dried egg and milk powders, pulverized
spices, starch and pastes, potato and woodflour, oil meal from beans and seed,
dried hay, and other organic materials which may produce combustible dusts when
processed or handled. Dusts containing magnesium or aluminum are particularly
hazardous and the use of extreme caution is necessary to avoid ignition and
explosion.
(ii) Class II, Division 2. A Class II, Division 2 location is a
location in which: (a) combustible dust will not normally be in
suspension in the air in quantities sufficient to produce explosive or ignitible
mixtures, and dust accumulations are normally insufficient to interfere with the
normal operation of electrical equipment or other apparatus; or (b) dust
may be in suspension in the air as a result of infrequent malfunctioning of
handling or processing equipment, and dust accumulations resulting therefrom may
be ignitible by abnormal operation or failure of electrical equipment or other
apparatus. Note: This classification includes locations where dangerous
concentrations of suspended dust would not be likely but where dust
accumulations might form on or in the vicinity of electric equipment. These
areas may contain equipment from which appreciable quantities of dust would
escape under abnormal operating conditions or be adjacent to a Class II Division
1 location, as described above, into which an explosive or ignitible
concentration of dust may be put into suspension under abnormal operating
conditions.
Class III locations. Class III locations are those that are hazardous
because of the presence of easily ignitible fibers or flyings but in which such
fibers or flyings are not likely to be in suspension in the air in quantities
sufficient to produce ignitible mixtures. Class III locations include the
following:
(i) Class III, Division 1. A Class III, Division 1 location is a
location in which easily ignitible fibers or materials producing combustible
flyings are handled, manufactured, or used. Note: Such locations usually include some parts of rayon, cotton, and
other textile mills; combustible fiber manufacturing and processing plants;
cotton gins and cotton-seed mills; flax-processing plants; clothing
manufacturing plants; woodworking plants, and establishments; and industries
involving similar hazardous processes or conditions.
Easily ignitible fibers and flyings include rayon, cotton (including cotton
linters and cotton waste), sisal or henequen, istle, jute, hemp, tow, cocoa
fiber, oakum, baled waste kapok, Spanish moss, excelsior, and other materials of
similar nature.
(ii) Class III, Division 2. A Class III, Division 2 location is a
location in which easily ignitible fibers are stored or handled, except in
process of manufacture.
Collector ring. A collector ring is an assembly of slip rings for
transferring electrical energy from a stationary to a rotating member.
Concealed. Rendered inaccessible by the structure or finish of the
building. Wires in concealed raceways are considered concealed, even though they
may become accessible by withdrawing them. [See Accessible. (As applied
to wiring methods.)]
Conductor. (i) Bare. A conductor having no covering or
electrical insulation whatsoever.
(ii) Covered. A conductor encased within material of composition or
thickness that is not recognized as electrical insulation.
(iii) Insulated. A conductor encased within material of composition
and thickness that is recognized as electrical insulation.
Conduit body. A separate portion of a conduit or tubing system that
provides access through a removable cover(s) to the interior of the system at a
junction of two or more sections of the system or at a terminal point of the
system. Boxes such as FS and FD or larger cast or sheet metal boxes are not
classified as conduit bodies.
Controller. A device or group of devices that serves to govern, in
some predetermined manner, the electric power delivered to the apparatus to
which it is connected.
Cooking unit, counter-mounted. A cooking appliance designed for
mounting in or on a counter and consisting of one or more heating elements,
internal wiring, and built-in or separately mountable controls. (See Oven,
wall-mounted.)
Covered conductor. See Conductor.
Cutout. (Over 600 volts, nominal.) An assembly of a fuse support with
either a fuseholder, fuse carrier, or disconnecting blade. The fuseholder or
fuse carrier may include a conducting element (fuse link), or may act as the
disconnecting blade by the inclusion of a nonfusible member.
Cutout box. An enclosure designed for surface mounting and having
swinging doors or covers secured directly to and telescoping with the walls of
the box proper. (See Cabinet.)
Damp location. See Location.
Dead front. Without live parts exposed to a person on the operating
side of the equipment.
Device. A unit of an electrical system which is intended to carry but
not utilize electric energy.
Dielectric heating. Dielectric heating is the heating of a nominally
insulating material due to its own dielectric losses when the material is placed
in a varying electric field.
Disconnecting means. A device, or group of devices, or other means by
which the conductors of a circuit can be disconnected from their source of
supply.
Disconnecting (or Isolating) switch. (Over 600 volts, nominal.) A
mechanical switching device used for isolating a circuit or equipment from a
source of power.
Dry location. See Location.
Electric sign. A fixed, stationary, or portable self-contained,
electrically illuminated utilization equipment with words or symbols designed to
convey information or attract attention.
Enclosed. Surrounded by a case, housing, fence or walls which will
prevent persons from accidentally contacting energized parts.
Enclosure. The case or housing of apparatus, or the fence or walls
surrounding an installation to prevent personnel from accidentally contacting
energized parts, or to protect the equipment from physical damage.
Equipment. A general term including material, fittings, devices,
appliances, fixtures, apparatus, and the like, used as a part of, or in
connection with, an electrical installation.
Equipment grounding conductor. See Grounding conductor,
equipment.
Explosion-proof apparatus. Apparatus enclosed in a case that is
capable of withstanding an explosion of a specified gas or vapor which may occur
within it and of preventing the ignition of a specified gas or vapor surrounding
the enclosure by sparks, flashes, or explosion of the gas or vapor within, and
which operates at such an external temperature that it will not ignite a
surrounding flammable atmosphere.
Exposed. (As applied to live parts.) Capable of being inadvertently
touched or approached nearer than a safe distance by a person. It is applied to
parts not suitably guarded, isolated, or insulated. (See Accessible. and
Concealed.)
Exposed. (As applied to wiring methods.) On or attached to the surface
or behind panels designed to allow access. [See Accessible. (As applied
to wiring methods.)]
Exposed. (For the purposes of § 1910.308(e),
Communications systems.) Where the circuit is in such a position that in
case of failure of supports or insulation, contact with another circuit may
result.
Externally operable. Capable of being operated without exposing the
operator to contact with live parts.
Feeder. All circuit conductors between the service equipment, or the
generator switchboard of an isolated plant, and the final branch-circuit
overcurrent device.
Fitting. An accessory such as a locknut, bushing, or other part of a
wiring system that is intended primarily to perform a mechanical rather than an
electrical function.
Fuse. (Over 600 volts, nominal.) An overcurrent protective device with
a circuit opening fusible part that is heated and severed by the passage of
overcurrent through it. A fuse comprises all the parts that form a unit capable
of performing the prescribed functions. It may or may not be the complete device
necessary to connect it into an electrical circuit.
Ground. A conducting connection, whether intentional or accidental,
between an electrical circuit or equipment and the earth, or to some conducting
body that serves in place of the earth.
Grounded. Connected to earth or to some conducting body that serves in
place of the earth.
Grounded, effectively. (Over 600 volts, nominal.) Permanently
connected to earth through a ground connection of sufficiently low impedance and
having sufficient ampacity that ground fault current which may occur cannot
build up to voltages dangerous to personnel.
Grounded conductor. A system or circuit conductor that is
intentionally grounded.
Grounding conductor. A conductor used to connect equipment or the
grounded circuit of a wiring system to a grounding electrode or electrodes.
Grounding conductor, equipment. The conductor used to connect the
non-current-carrying metal parts of equipment, raceways, and other enclosures to
the system grounded conductor and/or the grounding electrode conductor at the
service equipment or at the source of a separately derived system.
Grounding electrode conductor. The conductor used to connect the
grounding electrode to the equipment grounding conductor and/or to the grounded
conductor of the circuit at the service equipment or at the source of a
separately derived system.
Ground-fault circuit-interrupter. A device whose function is to
interrupt the electric circuit to the load when a fault current to ground
exceeds some predetermined value that is less than that required to operate the
overcurrent protective device of the supply circuit.
Guarded. Covered, shielded, fenced, enclosed, or otherwise protected
by means of suitable covers, casings, barriers, rails, screens, mats, or
platforms to remove the likelihood of approach to a point of danger or contact
by persons or objects.
Health care facilities. Buildings or portions of buildings and mobile
homes that contain, but are not limited to, hospitals, nursing homes, extended
care facilities, clinics, and medical and dental offices, whether fixed or
mobile.
Heating equipment. For the purposes of § 1910.306(g), the
term heating equipment includes any equipment used for heating purposes
if heat is generated by induction or dielectric methods.
Hoistway. Any shaftway, hatchway, well hole, or other vertical opening
or space in which an elevator or dumbwaiter is designed to operate.
Identified. Identified, as used in reference to a conductor or its
terminal, means that such conductor or terminal can be readily recognized as
grounded.
Induction heating. Induction heating is the heating of a nominally
conductive material due to its own I Insulated conductor. See Conductor.
Interrupter switch. (Over 600 volts, nominal.) A switch capable of
making, carrying, and interrupting specified currents.
Irrigation machine. An irrigation machine is an electrically driven or
controlled machine, with one or more motors, not hand portable, and used
primarily to transport and distribute water for agricultural purposes.
Isolated. Not readily accessible to persons unless special means for
access are used.
Isolated power system. A system comprising an isolating transformer or
its equivalent, a line isolation monitor, and its ungrounded circuit conductors.
Labeled. Equipment is labeled if there is attached to it a
label, symbol, or other identifying mark of a nationally recognized testing
laboratory which, (a) makes periodic inspections of the production of such
equipment, and (b) whose labeling indicates compliance with nationally
recognized standards or tests to determine safe use in a specified manner.
Lighting outlet. An outlet intended for the direct connection of a
lampholder, a lighting fixture, or a pendant cord terminating in a lampholder.
Line-clearance tree trimming. The pruning, trimming, repairing,
maintaining, removing, or clearing of trees or cutting of brush that is within
10 feet (305 cm) of electric supply lines and equipment.
Listed. Equipment is listed if it is of a kind mentioned in a
list which, (a) is published by a nationally recognized laboratory which makes
periodic inspection of the production of such equipment, and (b) states such
equipment meets nationally recognized standards or has been tested and found
safe for use in a specified manner.
Location -- (i) Damp location. Partially protected locations
under canopies, marquees, roofed open porches, and like locations, and interior
locations subject to moderate degrees of moisture, such as some basements, some
barns, and some cold-storage warehouses.
(ii) Dry location. A location not normally subject to dampness or
wetness. A location classified as dry may be temporarily subject to dampness or
wetness, as in the case of a building under construction.
(iii) Wet location. Installations underground or in concrete slabs or
masonry in direct contact with the earth, and locations subject to saturation
with water or other liquids, such as vehicle-washing areas, and locations
exposed to weather and unprotected.
May. If a discretionary right, privilege, or power is conferred, the
word "may" is used. If a right, privilege, or power is abridged or if an
obligation to abstain from acting is imposed, the word "may" is used with a
restrictive "no," "not," or "only." (E.g., no employer may
. . . ; an employer may not
. . . ; only qualified persons
may. . . .)
Medium voltage cable. Type MV medium voltage cable is a single or
multiconductor solid dielectric insulated cable rated 2000 volts or higher.
Metal-clad cable. Type MC cable is a factory assembly of one or more
conductors, each individually insulated and enclosed in a metallic sheath of
interlocking tape, or a smooth or corrugated tube.
Mineral-insulated metal-sheathed cable. Type MI mineral-insulated
metal-sheathed cable is a factory assembly of one or more conductors insulated
with a highly compressed refractory mineral insulation and enclosed in a
liquidtight and gastight continuous copper sheath.
Mobile X-ray. X-ray equipment mounted on a permanent base with wheels
and/or casters for moving while completely assembled.
Nonmetallic-sheathed cable. Nonmetallic-sheathed cable is a factory
assembly of two or more insulated conductors having an outer sheath of moisture
resistant, flame-retardant, nonmetallic material. Nonmetallic sheathed cable is
manufactured in the following types:
(i) Type NM. The overall covering has a flame-retardant and
moisture-resistant finish.
(ii) Type NMC. The overall covering is flame-retardant,
moisture-resistant, fungus-resistant, and corrosion-resistant.
Oil (filled) cutout. (Over 600 volts, nominal.) A cutout in which all
or part of the fuse support and its fuse link or disconnecting blade are mounted
in oil with complete immersion of the contacts and the fusible portion of the
conducting element (fuse link), so that arc interruption by severing of the fuse
link or by opening of the contacts will occur under oil.
Open wiring on insulators. Open wiring on insulators is an exposed
wiring method using cleats, knobs, tubes, and flexible tubing for the protection
and support of single insulated conductors run in or on buildings, and not
concealed by the building structure.
Outlet. A point on the wiring system at which current is taken to
supply utilization equipment.
Outline lighting. An arrangement of incandescent lamps or electric
discharge tubing to outline or call attention to certain features such as the
shape of a building or the decoration of a window.
Oven, wall-mounted. An oven for cooking purposes designed for mounting
in or on a wall or other surface and consisting of one of more heating elements,
internal wiring, and built-in or separately mountable controls. (See Cooking
unit, counter-mounted.)
Overcurrent. Any current in excess of the rated current of equipment
or the ampacity of a conductor. It may result from overload (see definition),
short circuit, or ground fault. A current in excess of rating may be
accommodated by certain equipment and conductors for a given set of conditions.
Hence the rules for overcurrent protection are specific for particular
situations.
Overload. Operation of equipment in excess of normal, full load
rating, or of a conductor in excess of rated ampacity which, when it persists
for a sufficient length of time, would cause damage or dangerous overheating. A
fault, such as a short circuit or ground fault, is not an overload. (See
Overcurrent.)
Panelboard. A single panel or group of panel units designed for
assembly in the form of a single panel; including buses, automatic overcurrent
devices, and with or without switches for the control of light, heat, or power
circuits; designed to be placed in a cabinet or cutout box placed in or against
a wall or partition and accessible only from the front. (See
Switchboard.)
Permanently installed decorative fountains and reflection pools. Those
that are constructed in the ground, on the ground, or in a building in such a
manner that the pool cannot be readily disassembled for storage and are served
by electrical circuits of any nature. These units are primarily constructed for
their aesthetic value and not intended for swimming or wading.
Permanently installed swimming pools, wading and therapeutic pools.
Those that are constructed in the ground, on the ground, or in a building in
such a manner that the pool cannot be readily disassembled for storage whether
or not served by electrical circuits of any nature.
Portable X-ray. X-ray equipment designed to be hand-carried.
Power and control tray cable. Type TC power and control tray cable is
a factory assembly of two or more insulated conductors, with or without
associated bare or covered grounding conductors under a nonmetallic sheath,
approved for installation in cable trays, in raceways, or where supported by a
messenger wire.
Power fuse. (Over 600 volts, nominal.) See Fuse.
Power-limited tray cable. Type PLTC nonmetallic-sheathed power limited
tray cable is a factory assembly of two or more insulated conductors under a
nonmetallic jacket.
Power outlet. An enclosed assembly which may include receptacles,
circuit breakers, fuseholders, fused switches, buses and watt-hour meter
mounting means; intended to supply and control power to mobile homes,
recreational vehicles or boats, or to serve as a means for distributing power
required to operate mobile or temporarily installed equipment.
Premises wiring system. That interior and exterior wiring, including
power, lighting, control, and signal circuit wiring together with all of its
associated hardware, fittings, and wiring devices, both permanently and
temporarily installed, which extends from the load end of the service drop, or
load end of the service lateral conductors to the outlet(s). Such wiring does
not include wiring internal to appliances, fixtures, motors, controllers, motor
control centers, and similar equipment.
Qualified person. One familiar with the construction and operation of
the equipment and the hazards involved. Note 1: Whether an employee is considered to be a "qualified person"
will depend upon various circumstances in the workplace. It is possible and, in
fact, likely for an individual to be considered "qualified" with regard to
certain equipment in the workplace, but "unqualified" as to other equipment.
(See § 1910.332(b)(3) for training requirements that specifically
apply to qualified persons.)
Note 2: An employee who is undergoing on-the-job training and who, in
the course of such training, has demonstrated an ability to perform duties
safely at his or her level of training and who is under the direct supervision
of a qualified person is considered to be a qualified person for the performance
of those duties.
Raceway. A channel designed expressly for holding wires, cables, or
busbars, with additional functions as permitted in this subpart. Raceways may be
of metal or insulating material, and the term includes rigid metal conduit,
rigid nonmetallic conduit, intermediate metal conduit, liquidtight flexible
metal conduit, flexible metallic tubing, flexible metal conduit, electrical
metallic tubing, underfloor raceways, cellular concrete floor raceways, cellular
metal floor raceways, surface raceways, wireways, and busways.
Readily accessible. Capable of being reached quickly for operation,
renewal, or inspections, without requiring those to whom ready access is
requisite to climb over or remove obstacles or to resort to portable ladders,
chairs, etc. (See Accessible.)
Receptacle. A receptacle is a contact device installed at the outlet
for the connection of a single attachment plug. A single receptacle is a single
contact device with no other contact device on the same yoke. A multiple
receptacle is a single device containing two or more receptacles.
Receptacle outlet. An outlet where one or more receptacles are
installed.
Remote-control circuit. Any electric circuit that controls any other
circuit through a relay or an equivalent device.
Sealable equipment. Equipment enclosed in a case or cabinet that is
provided with a means of sealing or locking so that live parts cannot be made
accessible without opening the enclosure. The equipment may or may not be
operable without opening the enclosure.
Separately derived system. A premises wiring system whose power is
derived from generator, transformer, or converter winding and has no direct
electrical connection, including a solidly connected grounded circuit conductor,
to supply conductors originating in another system.
Service. The conductors and equipment for delivering energy from the
electricity supply system to the wiring system of the premises served.
Service cable. Service conductors made up in the form of a cable.
Service conductors. The supply conductors that extend from the street
main or from transformers to the service equipment of the premises supplied.
Service drop. The overhead service conductors from the last pole or
other aerial support to and including the splices, if any, connecting to the
service-entrance conductors at the building or other structure.
Service-entrance cable. Service-entrance cable is a single conductor
or multiconductor assembly provided with or without an overall covering,
primarily used for services and of the following types:
(i) Type SE, having a flame-retardant, moisture-resistant covering,
but not required to have inherent protection against mechanical abuse.
(ii) Type USE, recognized for underground use, having a
moisture-resistant covering, but not required to have a flame-retardant covering
or inherent protection against mechanical abuse. Single-conductor cables having
an insulation specifically approved for the purpose do not require an outer
covering.
Service-entrance conductors, overhead system. The service conductors
between the terminals of the service equipment and a point usually outside the
building, clear of building walls, where joined by tap or splice to the service
drop.
Service entrance conductors, underground system. The service
conductors between the terminals of the service equipment and the point of
connection to the service lateral. Where service equipment is located outside
the building walls, there may be no service-entrance conductors, or they may be
entirely outside the building.
Service equipment. The necessary equipment, usually consisting of a
circuit breaker or switch and fuses, and their accessories, located near the
point of entrance of supply conductors to a building or other structure, or an
otherwise defined area, and intended to consititute the main control and means
of cutoff of the supply.
Service raceway. The raceway that encloses the service-entrance
conductors.
Shielded nonmetallic-sheathed cable. Type SNM, shielded
nonmetallic-sheathed cable is a factory assembly of two or more insulated
conductors in an extruded core of moisture-resistant, flame-resistant
nonmetallic material, covered with an overlapping spiral metal tape and wire
shield and jacketed with an extruded moisture-, flame-, oil-, corrosion-,
fungus-, and sunlight-resistant nonmetallic material.
Show window. Any window used or designed to be used for the display of
goods or advertising material, whether it is fully or partly enclosed or
entirely open at the rear and whether or not it has a platform raised higher
than the street floor level.
Sign. See Electric sign.
Signaling circuit. Any electric circuit that energizes signaling
equipment.
Special permission. The written consent of the authority having
jurisdiction.
Storable swimming or wading pool. A pool with a maximum dimension of
15 feet and a maximum wall height of 3 feet and is so constructed that it may be
readily disassembled for storage and reassembled to its original integrity.
Switchboard. A large single panel, frame, or assembly of panels which
have switches, buses, instruments, overcurrent and other protective devices
mounted on the face or back or both. Switchboards are generally accessible from
the rear as well as from the front and are not intended to be installed in
cabinets. (See Panelboard.)
Switches.
(i) General-use switch. A switch intended for use in general
distribution and branch circuits. It is rated in amperes, and it is capable of
interrupting its rated current at its rated voltage.
(ii) General-use snap switch. A form of general-use switch so
constructed that it can be installed in flush device boxes or on outlet box
covers, or otherwise used in conjunction with wiring systems recognized by this
subpart.
(iii) Isolating switch. A switch intended for isolating an electric
circuit from the source of power. It has no interrupting rating, and it is
intended to be operated only after the circuit has been opened by some other
means.
(iv) Motor-circuit switch. A switch, rated in horsepower, capable of
interrupting the maximum operating overload current of a motor of the same
horsepower rating as the switch at the rated voltage.
Switching devices. (Over 600 volts, nominal.) Devices designed to
close and/or open one or more electric circuits. Included in this category are
circuit breakers, cutouts, disconnecting (or isolating) switches, disconnecting
means, interrupter switches, and oil (filled) cutouts.
Transportable X-ray. X-ray equipment installed in a vehicle or that
may readily be disassembled for transport in a vehicle.
Utilization equipment. Utilization equipment means equipment which
utilizes electric energy for mechanical, chemical, heating, lighting, or similar
useful purpose.
Utilization system. A utilization system is a system which provides
electric power and light for employee workplaces, and includes the premises
wiring system and utilization equipment.
Ventilated. Provided with a means to permit circulation of air
sufficient to remove an excess of heat, fumes, or vapors.
Volatile flammable liquid. A flammable liquid having a flash point
below 38 degrees C (100 degrees F) or whose temperature is above its flash
point.
Voltage (of a circuit). The greatest root-mean-square (effective)
difference of potential between any two conductors of the circuit concerned.
Voltage, nominal. A nominal value assigned to a circuit or system for
the purpose of conveniently designating its voltage class (as 120/240, 480Y/277,
600, etc.). The actual voltage at which a circuit operates can vary from the
nominal within a range that permits satisfactory operation of equipment.
Voltage to ground. For grounded circuits, the voltage between the
given conductor and that point or conductor of the circuit that is grounded; for
ungrounded circuits, the greatest voltage between the given conductor and any
other conductor of the circuit.
Watertight. So constructed that moisture will not enter the enclosure.
Weatherproof. So constructed or protected that exposure to the weather
will not interfere with successful operation. Rainproof, raintight, or
watertight equipment can fulfill the requirements for weatherproof where varying
weather conditions other than wetness, such as snow, ice, dust, or temperature
extremes, are not a factor.
Wet location. See Location.
Wireways. Wireways are sheet-metal troughs with hinged or removable
covers for housing and protecting electric wires and cable and in which
conductors are laid in place after the wireway has been installed as a complete
system.
[46 FR 4056, Jan. 16, 1981; 46 FR 40185, Aug. 7, 1981, as amended at 53 FR
12123, Apr. 12, 1988; 55 FR 32020, Aug. 6, 1990; 55 FR 46054, Nov. 1,
1990]