|
||||||||||||
|
|
|
|
|
|
||||||||
|
|
29 CFR | | 40 CFR |
| 49 CFR |
| FR Daily |
| MSDS |
|Seton |
§ 1910.308 Special systems.
(a) Systems over 600 volts, nominal. Paragraphs (a) (1) through (4) of this section cover the general requirements for all circuits and equipment operated at over 600 volts.
(1) Wiring methods for fixed installations. (i) Above-ground conductors shall be installed in rigid metal conduit, in intermediate metal conduit, in cable trays, in cablebus, in other suitable raceways, or as open runs of metal-clad cable suitable for the use and purpose. However, open runs of non-metallic-sheathed cable or of bare conductors or busbars may be installed in locations accessible only to qualified persons. Metallic shielding components, such as tapes, wires, or braids for conductors, shall be grounded. Open runs of insulated wires and cables having a bare lead sheath or a braided outer covering shall be supported in a manner designed to prevent physical damage to the braid or sheath.
(ii) Conductors emerging from the ground shall be enclosed in approved raceways. (See § 1910.302(b)(3).)
(2) Interrupting and isolating devices. (i) Circuit breaker installations located indoors shall consist of metal-enclosed units or fire-resistant cell-mounted units. In locations accessible only to qualified personnel, open mounting of circuit breakers is permitted. A means of indicating the open and closed position of circuit breakers shall be provided.
(ii) Fused cutouts installed in buildings or tranformer vaults shall be of a type approved for the purpose. They shall be readily accessible for fuse replacement.
(iii) A means shall be provided to completely isolate equipment for inspection and repairs. Isolating means which are not designed to interrupt the load curent of the circuit shall be either interlocked with an approved circuit interrupter or provided with a sign warning against opening them under load.
(3) Mobile and portable equipment. (i) Power cable connections to mobile machines. A metallic enclosure shall be provided on the mobile machine for enclosing the terminals of the power cable. The enclosure shall include provisions for a solid connection for the ground wire(s) terminal to effectively ground the machine frame. The method of cable termination used shall prevent any strain or pull on the cable from stressing the electrical connections. The enclosure shall have provision for locking so only authorized qualified persons may open it and shall be marked with a sign warning of the presence of energized parts.
(ii) Guarding live parts. All energized switching and control parts shall be enclosed in effectively grounded metal cabinets or enclosures. Circuit breakers and protective equipment shall have the operating means projecting through the metal cabinet or enclosure so these units can be reset without locked doors being opened. Enclosures and metal cabinets shall be locked so that only authorized qualified persons have access and shall be marked with a sign warning of the presence of energized parts. Collector ring assemblies on revolving-type machines (shovels, draglines, etc.) shall be guarded.
(4) Tunnel installation -- (i) Application. The provisions of this paragraph apply to installation and use of high-voltage power distribution and utilization equipment which is portable and/or mobile, such as substations, trailers, cars, mobile shovels, draglines, hoists, drills, dredges, compressors, pumps, conveyors, and underground excavators.
(ii) Conductors. Conductors in tunnels shall be installed in one or more of the following:
(A) Metal conduit or other metal raceway,
(B) Type MC cable, or
(C) Other approved multiconductor cable. (iii) Guarding live parts. Bare terminals of transformers, switches,
motor controllers, and other equipment shall be enclosed to prevent accidental
contact with energized parts. Enclosures for use in tunnels shall be drip-proof,
weatherproof, or submersible as required by the environmental conditions.
(iv) Disconnecting means. A disconnecting means that simultaneously
opens all ungrounded conductors shall be installed at each transformer or motor
location.
(v) Grounding and bonding. All nonenergized metal parts of electric
equipment and metal raceways and cable sheaths shall be effectively grounded and
bonded to all metal pipes and rails at the portal and at intervals not exceeding
1000 feet throughout the tunnel.
(b) Emergency power systems -- (1) Scope. The provisions for
emergency systems apply to circuits, systems, and equipment intended to supply
power for illumination and special loads, in the event of failure of the normal
supply.
(2) Wiring methods. Emergency circuit wiring shall be kept entirely
independent of all other wiring and equipment and may not enter the same
raceway, cable, box, or cabinet or other wiring except either where common
circuit elements suitable for the purpose are required, or for transferring
power from the normal to the emergency source.
(3) Emergency illumination. Where emergency lighting is necessary, the
system shall be so arranged that the failure of any individual lighting element,
such as the burning out of a light bulb, cannot leave any space in total
darkness.
(c) Class 1, Class 2, and Class 3 remote control, signaling, and
power-limited circuits -- (1) Classification. Class 1, Class 2, or
Class 3 remote control, signaling, or power-limited circuits are characterized
by their usage and electrical power limitation which differentiates them from
light and power circuits. These circuits are classified in accordance with their
respective voltage and power limitations as summarized in paragraphs (c)(1)(i)
through (c)(1)(iii) of this section.
(i) Class 1 circuits. (A) A Class 1 power-limited circuit is supplied
from a source having a rated output of not more than 30 volts and 1000
volt-amperes.
(B) A Class 1 remote control circuit or a Class 1 signaling circuit has a
voltage which does not exceed 600 volts; however, the power output of the source
need not be limited.
(ii) Class 2 and Class 3 circuits. (A) Power for Class 2 and Class 3
circuits is limited either inherently (in which no overcurrent protection is
required) or by a combination of a power source and overcurrent protection.
(B) The maximum circuit voltage is 150 volts AC or DC for a Class 2
inherently limited power source, and 100 volts AC or DC for a Class 3 inherently
limited power source.
(C) The maximum circuit voltage is 30 volts AC and 60 volts DC for a Class 2
power source limited by overcurrent protection, and 150 volts AC or DC for a
Class 3 power source limited by overcurrent protection.
(iii) The maximum circuit voltages in paragraphs (c)(1)(i) and (c)(1)(ii) of
this section apply to sinusoidal AC or continuous DC power sources, and where
wet contact occurence is not likely.
(2) Marking. A Class 2 or Class 3 power supply unit shall be durably
marked where plainly visible to indicate the class of supply and its electrical
rating. (See § 1910.302(b)(3).)
(d) Fire protective signaling systems. (See
§ 1910.302(b)(3).)
(1) Classifications. Fire protective signaling circuits shall be
classified either as non-power limited or power limited.
(2) Power sources. The power sources for use with fire protective
signaling circuits shall be either power limited or nonlimited as follows:
(i) The power supply of non-power-limited fire protective signaling circuits
shall have an output voltage not in excess of 600 volts.
(ii) The power for power-limited fire protective signaling circuits shall be
either inherently limited, in which no overcurrent protection is required, or
limited by a combination of a power source and overcurrent protection.
(3) Non-power-limited conductor location. Non-power-limited fire
protective signaling circuits and Class 1 circuits may occupy the same
enclosure, cable, or raceway provided all conductors are insulated for maximum
voltage of any conductor within the enclosure, cable, or raceway. Power supply
and fire protective signaling circuit conductors are permitted in the same
enclosure, cable, or raceway only if connected to the same equipment.
(4) Power-limited conductor location. Where open conductors are
installed, power-limited fire protective signaling circuits shall be separated
at least 2 inches from conductors of any light, power, Class 1, and
non-power-limited fire protective signaling circuits unless a special and
equally protective method of conductor separation is employed. Cables and
conductors of two or more power-limited fire protective signaling circuits or
Class 3 circuits are permitted in the same cable, enclosure, or raceway.
Conductors of one or more Class 2 circuits are permitted within the same cable,
enclosure, or raceway with conductors of power-limited fire protective signaling
circuits provided that the insulation of Class 2 circuit conductors in the
cable, enclosure, or raceway is at least that needed for the power-limited fire
protective signaling circuits.
(5) Identification. Fire protective signaling circuits shall be
identified at terminal and junction locations in a manner which will prevent
unintentional interference with the signaling circuit during testing and
servicing. Power-limited fire protective signaling circuits shall be durably
marked as such where plainly visible at terminations.
(e) Communications systems -- (1) Scope. These provisions for
communication systems apply to such systems as central-station-connected and
non-central-station-connected telephone circuits, radio and television receiving
and transmitting equipment, including community antenna television and radio
distribution systems, telegraph, district messenger, and outside wiring for fire
and burglar alarm, and similar central station systems. These installations need
not comply with the provisions of §§ 1910.303 through 1910.308(d),
except § 1910.304(c)(1) and § 1910.307(b).
(2) Protective devices. (i) Communication circuits so located as to be
exposed to accidental contact with light or power conductors operating at over
300 volts shall have each circuit so exposed provided with a protector approved
for the purpose.
(ii) Each conductor of a lead-in from an outdoor antenna shall be provided
with an antenna discharge unit or other suitable means that will drain static
charges from the antenna system.
(3) Conductor location -- (i) Outside of buildings. (a)
Receiving distribution lead-in or aerial-drop cables attached to buildings and
lead-in conductors to radio transmitters shall be so installed as to avoid the
possibility of accidental contact with electric light or power conductors.
(b) The clearance between lead-in conductors and any lightning
protection conductors may not be less than 6 feet.
(ii) On poles. Where practicable, communication conductors on poles
shall be located below the light or power conductors. Communications conductors
may not be attached to a crossarm that carries light or power conductors.
(iii) Inside of buildings. Indoor antennas, lead-ins, and other
communication conductors attached as open conductors to the inside of buildings
shall be located at least 2 inches from conductors of any light or power or
Class 1 circuits unless a special and equally protective method of conductor
separation, approved for the purpose, is employed.
(4) Equipment location. Outdoor metal structures supporting antennas,
as well as self-supporting antennas such as vertical rods or dipole structures,
shall be located as far away from overhead conductors of electric light and
power circuits of over 150 volts to ground as necessary to avoid the possibility
of the antenna or structure falling into or making accidental contact with such
circuits.
(5) Grounding -- (i) Lead-in conductors. If exposed to contact
with electric light and power conductors, the metal sheath of aerial cables
entering buildings shall be grounded or shall be interrupted close to the
entrance to the building by an insulating joint or equivalent device. Where
protective devices are used, they shall be grounded in an approved manner.
(ii) Antenna structures. Masts and metal structures supporting
antennas shall be permanently and effectively grounded without splice or
connection in the grounding conductor.
(iii) Equipment enclosures. Transmitters shall be enclosed in a metal
frame or grill or separated from the operating space by a barrier, all metallic
parts of which are effectively connected to ground. All external metal handles
and controls accessible to the operating personnel shall be effectively
grounded. Unpowered equipment and enclosures shall be considered grounded where
connected to an attached coaxial cable with an effectively grounded metallic
shield.
[46 FR 4056, Jan. 16, 1981; 46 FR 40185, Aug. 7, 1981]