|
||||||||||||
|
|
|
|
|
|
||||||||
|
|
29 CFR | | 40 CFR |
| 49 CFR |
| FR Daily |
| MSDS |
|Seton |
§ 1910.303 General requirements.
(a) Approval. The conductors and equipment required or permitted by this subpart shall be acceptable only if approved.
(b) Examination, installation, and use of equipment -- (1) Examination. Electrical equipment shall be free from recognized hazards that are likely to cause death or serious physical harm to employees. Safety of equipment shall be determined using the following considerations:
(i) Suitability for installation and use in conformity with the provisions of this subpart. Suitability of equipment for an identified purpose may be evidenced by listing or labeling for that identified purpose.
(ii) Mechanical strength and durability, including, for parts designed to enclose and protect other equipment, the adequacy of the protection thus provided.
(iii) Electrical insulation.
(iv) Heating effects under conditions of use.
(v) Arcing effects.
(vi) Classification by type, size, voltage, current capacity, specific use.
(vii) Other factors which contribute to the practical safeguarding of employees using or likely to come in contact with the equipment.
(2) Installation and use. Listed or labeled equipment shall be used or installed in accordance with any instructions included in the listing or labeling.
(c) Splices. Conductors shall be spliced or joined with splicing devices suitable for the use or by brazing, welding, or soldering with a fusible metal or alloy. Soldered splices shall first be so spliced or joined as to be mechanically and electrically secure without solder and then soldered. All splices and joints and the free ends of conductors shall be covered with an insulation equivalent to that of the conductors or with an insulating device suitable for the purpose.
(d) Arcing parts. Parts of electric equipment which in ordinary operation produce arcs, sparks, flames, or molten metal shall be enclosed or separated and isolated from all combustible material.
(e) Marking. Electrical equipment may not be used unless the manufacturer's name, trademark, or other descriptive marking by which the organization responsible for the product may be identified is placed on the equipment. Other markings shall be provided giving voltage, current, wattage, or other ratings as necessary. The marking shall be of sufficient durability to withstand the environment involved.
(f) Identification of disconnecting means and circuits. Each disconnecting means required by this subpart for motors and appliances shall be legibly marked to indicate its purpose, unless located and arranged so the purpose is evident. Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, shall be legibly marked to indicate its purpose, unless located and arranged so the purpose is evident. These markings shall be of sufficient durability to withstand the environment involved.
(g) 600 Volts, nominal, or less -- (1) Working space about electric equipment. Sufficient access and working space shall be provided and maintained about all electric equipment to permit ready and safe operation and maintenance of such equipment.
(i) Working clearances. Except as required or permitted elsewhere in this subpart, the dimension of the working space in the direction of access to live parts operating at 600 volts or less and likely to require examination, adjustment, servicing, or maintenance while alive may not be less than indicated in Table S-1. In addition to the dimensions shown in Table S-1, workspace may not be less than 30 inches wide in front of the electric equipment. Distances shall be measured from the live parts if they are exposed, or from the enclosure front or opening if the live parts are enclosed. Concrete, brick, or tile walls are considered to be grounded. Working space is not required in back of assemblies such as dead-front switchboards or motor control centers where there are no renewable or adjustable parts such as fuses or switches on the back and where all connections are accessible from locations other than the back.
Table S-1--Working Clearances
------------------------------------------------------------------------
Minimum clear distance
for condition\2\ (ft)
Nominal voltage to ground --------------------------
(a) (b) (c)
------------------------------------------------------------------------
0-150........................................ \1\3 \1\3 3
151-600...................................... \1\3 3\1/2\ 4
------------------------------------------------------------------------
\1\Minimum clear distances may be 2 feet 6 inches for installations
built prior to April 16, 1981.
\2\Conditions (a), (b), and (c), are as follows: (a) Exposed live parts
on one side and no live or grounded parts on the other side of the
working space, or exposed live parts on both sides effectively guarded
by suitable wood or other insulating material. Insulated wire or
insulated busbars operating at not over 300 volts are not considered
live parts. (b) Exposed live parts on one side and grounded parts on
the other side. (c) Exposed live parts on both sides of the workspace
[not guarded as provided in Condition (a)] with the operator between.
(ii) Clear spaces. Working space required by this subpart may not be used for storage. When normally enclosed live parts are exposed for inspection or servicing, the working space, if in a passageway or general open space, shall be suitably guarded.
(iii) Access and entrance to working space. At least one entrance of sufficient area shall be provided to give access to the working space about electric equipment.
(iv) Front working space. Where there are live parts normally exposed on the front of switchboards or motor control centers, the working space in front of such equipment may not be less than 3 feet.
(v) Illumination. Illumination shall be provided for all working spaces about service equipment, switchboards, panelboards, and motor control centers installed indoors.
(vi) Headroom. The minimum headroom of working spaces about service
equipment, switchboards, panel-boards, or motor control centers shall be 6 feet
3 inches. Note: As used in this section a motor control center is an assembly of
one or more enclosed sections having a common power bus and principally
containing motor control units.
(2) Guarding of live parts. (i) Except as required or permitted
elsewhere in this subpart, live parts of electric equipment operating at 50
volts or more shall be guarded against accidental contact by approved cabinets
or other forms of approved enclosures, or by any of the following means:
(A) By location in a room, vault, or similar enclosure that is accessible
only to qualified persons.
(B) By suitable permanent, substantial partitions or screens so arranged that
only qualified persons will have access to the space within reach of the live
parts. Any openings in such partitions or screens shall be so sized and located
that persons are not likely to come into accidental contact with the live parts
or to bring conducting objects into contact with them.
(C) By location on a suitable balcony, gallery, or platform so elevated and
arranged as to exclude unqualified persons.
(D) By elevation of 8 feet or more above the floor or other working surface.
(ii) In locations where electric equipment would be exposed to physical
damage, enclosures or guards shall be so arranged and of such strength as to
prevent such damage.
(iii) Entrances to rooms and other guarded locations containing exposed live
parts shall be marked with conspicuous warning signs forbidding unqualified
persons to enter.
(h) Over 600 volts, nominal -- (1) General. Conductors and
equipment used on circuits exceeding 600 volts, nominal, shall comply with all
applicable provisions of paragraphs (a) through (g) of this section and with the
following provisions which supplement or modify those requirements. The
provisions of paragraphs (h)(2), (h)(3), and (h)(4) of this section do not apply
to equipment on the supply side of the service conductors.
(2) Enclosure for electrical installations. Electrical installations
in a vault, room, closet or in an area surrounded by a wall, screen, or fence,
access to which is controlled by lock and key or other approved means, are
considered to be accessible to qualified persons only. A wall, screen, or fence
less than 8 feet in height is not considered to prevent access unless it has
other features that provide a degree of isolation equivalent to an 8 foot fence.
The entrances to all buildings, rooms, or enclosures containing exposed live
parts or exposed conductors operating at over 600 volts, nominal, shall be kept
locked or shall be under the observation of a qualified person at all times.
(i) Installations accessible to qualified persons only. Electrical
installations having exposed live parts shall be accessible to qualified persons
only and shall comply with the applicable provisions of paragraph (h)(3) of this
section.
(ii) Installations accessible to unqualified persons. Electrical
installations that are open to unqualified persons shall be made with
metal-enclosed equipment or shall be enclosed in a vault or in an area, access
to which is controlled by a lock. If metal-enclosed equipment is installed so
that the bottom of the enclosure is less than 8 feet above the floor, the door
or cover shall be kept locked. Metal-enclosed switchgear, unit substations,
transformers, pull boxes, connection boxes, and other similar associated
equipment shall be marked with appropriate caution signs. If equipment is
exposed to physical damage from vehicular traffic, suitable guards shall be
provided to prevent such damage. Ventilating or similar openings in
metal-enclosed equipment shall be designed so that foreign objects inserted
through these openings will be deflected from energized parts.
(3) Workspace about equipment. Sufficient space shall be provided and
maintained about electric equipment to permit ready and safe operation and
maintenance of such equipment. Where energized parts are exposed, the minimum
clear workspace may not be less than 6 feet 6 inches high (measured vertically
from the floor or platform), or less than 3 feet wide (measured parallel to the
equipment). The depth shall be as required in Table S-2. The workspace shall be
adequate to permit at least a 90-degree opening of doors or hinged panels.
(i) Working space. The minimum clear working space in front of
electric equipment such as switchboards, control panels, switches, circuit
breakers, motor controllers, relays, and similar equipment may not be less than
specified in Table S-2 unless otherwise specified in this subpart. Distances
shall be measured from the live parts if they are exposed, or from the enclosure
front or opening if the live parts are enclosed. However, working space is not
required in back of equipment such as deadfront switchboards or control
assemblies where there are no renewable or adjustable parts (such as fuses or
switches) on the back and where all connections are accessible from locations
other than the back. Where rear access is required to work on de-energized parts
on the back of enclosed equipment, a minimum working space of 30 inches
horizontally shall be provided. (ii) Illumination. Adequate illumination shall be provided for all
working spaces about electric equipment. The lighting outlets shall be so
arranged that persons changing lamps or making repairs on the lighting system
will not be endangered by live parts or other equipment. The points of control
shall be so located that persons are not likely to come in contact with any live
part or moving part of the equipment while turning on the lights.
(iii) Elevation of unguarded live parts. Unguarded live parts above
working space shall be maintained at elevations not less than specified in Table
S-3. (4) Entrance and access to workspace. (See
§ 1910.302(b)(3).)
(i) At least one entrance not less than 24 inches wide and 6 feet 6 inches
high shall be provided to give access to the working space about electric
equipment. On switchboard and control panels exceeding 48 inches in width, there
shall be one entrance at each end of such board where practicable. Where bare
energized parts at any voltage or insulated energized parts above 600 volts are
located adjacent to such entrance, they shall be suitably guarded.
(ii) Permanent ladders or stairways shall be provided to give safe access to
the working space around electric equipment installed on platforms, balconies,
mezzanine floors, or in attic or roof rooms or spaces.
[46 FR 4056, Jan. 16, 1981; 46 FR 40185, Aug. 7, 1981] Table S-2--Minimum Depth of Clear Working Space in Front of Electric
Equipment
------------------------------------------------------------------------
Conditions\2\ (ft)
Nominal voltage to ground --------------------------
(a) (b) (c)
------------------------------------------------------------------------
601 to 2,500................................. 3 4 5
2,501 to 9,000............................... 4 5 6
9,001 to 25,000.............................. 5 6 9
25,001 to 75kV\1\............................ 6 8 10
Above 75kV\1\................................ 8 10 12
------------------------------------------------------------------------
\1\Minimum depth of clear working space in front of electric equipment
with a nominal voltage to ground above 25,000 volts may be the same as
for 25,000 volts under Conditions (a), (b), and (c) for installations
built prior to April 16, 1981.
\2\Conditions (a), (b), and (c) are as follows: (a) Exposed live parts
on one side and no live or grounded parts on the other side of the
working space, or exposed live parts on both sides effectively guarded
by suitable wood or other insulating materials. Insulated wire or
insulated busbars operating at not over 300 volts are not considered
live parts. (b) Exposed live parts on one side and grounded parts on
the other side. Concrete, brick, or tile walls will be considered as
grounded surfaces. (c) Exposed live parts on both sides of the
workspace not guarded as provided in Condition (a) with the operator
between.
Table S-3--Elevation of Unguarded Energized Parts Above Working Space
------------------------------------------------------------------------
Nominal voltage between phases Minimum elevation
------------------------------------------------------------------------
601 to 7,500.............................. *8 feet 6 inches.
7,501 to 35,000........................... 9 feet.
Over 35kV................................. 9 feet + 0.37 inches per kV
above 35kV.
------------------------------------------------------------------------
*Note.--Minimum elevation may be 8 feet 0 inches for installations built
prior to April 16, 1981 if the nominal voltage between phases is in
the range of 601-6600 volts.