§ 1910.137 Electrical protective equipment.
(a) Design requirements. Insulating blankets, matting, covers, line hose, gloves, and sleeves made of rubber shall meet the following requirements:
(1) Manufacture and marking. (i) Blankets, gloves, and sleeves shall be produced by a seamless process.
(ii) Each item shall be clearly marked as follows:
(A) Class 0 equipment shall be marked Class 0.
(B) Class 1 equipment shall be marked Class 1.
(C) Class 2 equipment shall be marked Class 2.
(D) Class 3 equipment shall be marked Class 3.
(E) Class 4 equipment shall be marked Class 4.
(F) Non-ozone-resistant equipment other than matting shall be marked Type I.
(G) Ozone-resistant equipment other than matting shall be marked Type II.
(H) Other relevant markings, such as the manufacturer's identification and the size of the equipment, may also be provided.
(iii) Markings shall be nonconducting and shall be applied in such a manner as not to impair the insulating qualities of the equipment.
(iv) Markings on gloves shall be confined to the cuff portion of the glove.
(2) Electrical requirements. (i) Equipment shall be capable of withstanding the a-c proof-test voltage specified in Table I-2 or the d-c proof-test voltage specified in Table I-3.
(A) The proof test shall reliably indicate that the equipment can withstand the voltage involved.
(B) The test voltage shall be applied continuously for 3 minutes for equipment other than matting and shall be applied continuously for 1 minute for matting.
(C) Gloves shall also be capable of withstanding the a-c proof-test voltage specified in Table I-2 after a 16-hour water soak. (See the note following paragraph (a)(3)(ii)(B) of this section.)
(ii) When the a-c proof test is used on gloves, the 60-hertz proof-test current may not exceed the values specified in Table I-2 at any time during the test period.
(A) If the a-c proof test is made at a frequency other than 60 hertz, the permissible proof-test current shall be computed from the direct ratio of the frequencies.
(B) For the test, gloves (right side out) shall be filled with tap water and immersed in water to a depth that is in accordance with Table I-4. Water shall be added to or removed from the glove, as necessary, so that the water level is the same inside and outside the glove.
(C) After the 16-hour water soak specified in paragraph (a)(2)(i)(C) of this section, the 60-hertz proof-test current may exceed the values given in Table I-2 by not more than 2 milliamperes.
(iii) Equipment that has been subjected to a minimum breakdown voltage test may not be used for electrical protection. (See the note following paragraph (a)(3)(ii)(B) of this section.)
(iv) Material used for Type II insulating equipment shall be capable of withstanding an ozone test, with no visible effects. The ozone test shall reliably indicate that the material will resist ozone exposure in actual use. Any visible signs of ozone deterioration of the material, such as checking, cracking, breaks, or pitting, is evidence of failure to meet the requirements for ozone-resistant material. (See the note following paragraph (a)(3)(ii)(B) of this section.)
(3) Workmanship and finish. (i) Equipment shall be free of harmful physical irregularities that can be detected by the tests or inspections required under this section.
(ii) Surface irregularities that may be present on all rubber goods because of imperfections on forms or molds or because of inherent difficulties in the manufacturing process and that may appear as indentations, protuberances, or imbedded foreign material are acceptable under the following conditions:
(A) The indentation or protuberance blends into a smooth slope when the material is stretched.
(B) Foreign material remains in place when the insulating material is folded
and stretches with the insulating material surrounding it. Note: Rubber insulating equipment meeting the following national
consensus standards is deemed to be in compliance with paragraph (a) of this
section:
ASTM D 178-93 (or D 178-88) Specification for Rubber Insulating Matting.
ASTM D 1048-93 (or D 1048-88a) Specification for Rubber Insulating Blankets.
ASTM D 1049-93 (or D 1049-88) Specification for Rubber Insulating Covers.
ASTM D 1050-90, Specification for Rubber Insulating Line Hose.
ASTM D 1051-87, Specification for Rubber Insulating Sleeves.
These standards contain specifications for conducting the various tests
required in paragraph (a) of this section. For example, the a-c and d-c proof
tests, the breakdown test, the water soak procedure, and the ozone test
mentioned in this paragraph are described in detail in the ASTM standards.
(b) In-service care and use. (1) Electrical protective equipment shall
be maintained in a safe, reliable condition.
(2) The following specific requirements apply to insulating blankets, covers,
line hose, gloves, and sleeves made of rubber:
(i) Maximum use voltages shall conform to those listed in Table I-5.
(ii) Insulating equipment shall be inspected for damage before each day's use
and immediately following any incident that can reasonably be suspected of
having caused damage. Insulating gloves shall be given an air test, along with
the inspection.
(iii) Insulating equipment with any of the following defects may not be used:
(A) A hole, tear, puncture, or cut;
(B) Ozone cutting or ozone checking (the cutting action produced by ozone on
rubber under mechanical stress into a series of interlacing cracks);
(C) An embedded foreign object;
(D) Any of the following texture changes: swelling, softening, hardening, or
becoming sticky or inelastic.
(E) Any other defect that damages the insulating properties.
(iv) Insulating equipment found to have other defects that might affect its
insulating properties shall be removed from service and returned for testing
under paragraphs (b)(2)(viii) and (b)(2)(ix) of this section.
(v) Insulating equipment shall be cleaned as needed to remove foreign
substances.
(vi) Insulating equipment shall be stored in such a location and in such a
manner as to protect it from light, temperature extremes, excessive humidity,
ozone, and other injurious substances and conditions.
(vii) Protector gloves shall be worn over insulating gloves, except as
follows:
(A) Protector gloves need not be used with Class 0 gloves, under limited-use
conditions, where small equipment and parts manipulation necessitate unusually
high finger dexterity. Note: Extra care is needed in the visual examination of the glove and
in the avoidance of handling sharp objects.
(B) Any other class of glove may be used for similar work without protector
gloves if the employer can demonstrate that the possibility of physical damage
to the gloves is small and if the class of glove is one class higher than that
required for the voltage involved. Insulating gloves that have been used without
protector gloves may not be used at a higher voltage until they have been tested
under the provisions of paragraphs (b)(2)(viii) and (b)(2)(ix) of this section.
(viii) Electrical protective equipment shall be subjected to periodic
electrical tests. Test voltages and the maximum intervals between tests shall be
in accordance with Table I-5 and Table I-6.
(ix) The test method used under paragraphs (b)(2)(viii) and (b)(2)(ix) of
this section shall reliably indicate whether the insulating equipment can
withstand the voltages involved. Note: Standard electrical test methods considered as meeting this
requirement are given in the following national consensus standards:
American Society for Testing and Materials (ASTM) D 120-87, Specification for
Rubber Insulating Gloves.
ASTM D 1048-93, Specification for Rubber Insulating Blankets.
ASTM D 1049-93, Specification for Rubber Insulating Covers.
ASTM D 1050-90, Specification for Rubber Insulating Line Hose.
ASTM D 1051-87, Specification for Rubber Insulating Sleeves.
ASTM F 478-92, Specification for In-Service Care of Insulating Line Hose and
Covers.
ASTM F 479-93, Specification for In-Service Care of Insulating Blankets.
ASTM F 496-93b Specification for In-Service Care of Insulating Gloves and
Sleeves.
(x) Insulating equipment failing to pass inspections or electrical tests may
not be used by employees, except as follows:
(A) Rubber insulating line hose may be used in shorter lengths with the
defective portion cut off.
(B) Rubber insulating blankets may be repaired using a compatible patch that
results in physical and electrical properties equal to those of the blanket.
(C) Rubber insulating blankets may be salvaged by severing the defective area
from the undamaged portion of the blanket. The resulting undamaged area may not
be smaller than 22 inches by 22 inches (560 mm by 560 mm) for Class 1, 2, 3, and
4 blankets.
(D) Rubber insulating gloves and sleeves with minor physical defects, such as
small cuts, tears, or punctures, may be repaired by the application of a
compatible patch. Also, rubber insulating gloves and sleeves with minor surface
blemishes may be repaired with a compatible liquid compound. The patched area
shall have electrical and physical properties equal to those of the surrounding
material. Repairs to gloves are permitted only in the area between the wrist and
the reinforced edge of the opening.
(xi) Repaired insulating equipment shall be retested before it may be used by
employees.
(xii) The employer shall certify that equipment has been tested in accordance
with the requirements of paragraphs (b)(2)(viii), (b)(2)(ix), and (b)(2)(xi) of
this section. The certification shall identify the equipment that passed the
test and the date it was tested. Note: Marking of equipment and entering the results of the tests and
the dates of testing onto logs are two acceptable means of meeting this
requirement.
Note: The d-c voltages listed in this table are not appropriate for
proof testing rubber insulating line hose or covers. For this equipment, d-c
proof tests shall use a voltage high enough to indicate that the equipment can
be safely used at the voltages listed in Table I-4. See ASTM D 1050-90 and ASTM
D 1049-88 for further information on proof tests for rubber insulating line hose
and covers.
[59 FR 4435, Jan. 31, 1994; 59 FR 33662, June 30, 1994]
American Society for Testing and Materials (ASTM) D 120-87,
Specification for Rubber Insulating Gloves.
Table I-2--A-C Proof-Test Requirements
----------------------------------------------------------------------------------------------------------------
Maximum proof-test current, mA (gloves only)
Proof-test -----------------------------------------------
Class of equipment voltage 267-mm
rms V (10.5-in) 356-mm (14- 406-mm (16- 457-mm (18-
glove in) glove in) glove in) glove
----------------------------------------------------------------------------------------------------------------
0................................................... 5,000 8 12 14 16
1................................................... 10,000 .......... 14 16 18
2................................................... 20,000 .......... 16 18 20
3................................................... 30,000 .......... 18 20 22
4................................................... 40,000 .......... .......... 22 24
----------------------------------------------------------------------------------------------------------------
Table I-3--D-C Proof-Test Requirements
------------------------------------------------------------------------
Proof-test
Class of equipment voltage
------------------------------------------------------------------------
0.......................................................... 20,000
1.......................................................... 40,000
2.......................................................... 50,000
3.......................................................... 60,000
4.......................................................... 70,000
------------------------------------------------------------------------
Table I-4--Glove Tests--Water Level\1, 2\
------------------------------------------------------------------------
AC proof test DC proof test
Class of glove -------------------------------
mm. in. mm. in.
------------------------------------------------------------------------
0....................................... 38 1.5 38 1.5
1....................................... 38 1.5 51 2.0
2....................................... 64 2.5 76 3.0
3....................................... 89 3.5 102 4.0
4....................................... 127 5.0 153 6.0
------------------------------------------------------------------------
\1\The water level is given as the clearance from the cuff of the glove
to the water line, with a tolerance of <plus-minus>13 mm. (<plus-
minus>0.5 in.).
\2\If atmospheric conditions make the specified clearances impractical,
the clearances may be increased by a maximum of 25 mm. (1 in.).
Table I-5--Rubber Insulating Equipment Voltage Requirements
----------------------------------------------------------------------------------------------------------------
Maximum use Retest Retest
Class of equipment voltage\1\ a- voltage\2\ a- voltage\2\ d-
c--rms c--rms c--avg
----------------------------------------------------------------------------------------------------------------
0............................................................... 1,000 5,000 20,000
1............................................................... 7,500 10,000 40,000
2............................................................... 17,000 20,000 50,000
3............................................................... 26,500 30,000 60,000
4............................................................... 36,000 40,000 70,000
----------------------------------------------------------------------------------------------------------------
\1\The maximum use voltage is the a-c voltage (rms) classification of the protective equipment that designates
the maximum nominal design voltage of the energized system that may be safely worked. The nominal design
voltage is equal to the phase-to-phase voltage on multiphase circuits. However, the phase-to-ground potential
is considered to be the nominal design voltage:
(1) If there is no multiphase exposure in a system area and if the voltage exposure is limited to the phase-to-
ground potential, or
(2) If the electrical equipment and devices are insulated or isolated or both so that the multiphase exposure on
a grounded wye circuit is removed.
\2\The proof-test voltage shall be applied continuously for at least 1 minute, but no more than 3 minutes.
Table I-6--Rubber Insulating Equipment Test Intervals
------------------------------------------------------------------------
Type of equipment When to test
------------------------------------------------------------------------
Rubber insulating line hose............ Upon indication that insulating
value is suspect.
Rubber insulating covers............... Upon indication that insulating
value is suspect.
Rubber insulating blankets............. Before first issue and every 12
months thereafter.\1\
Rubber insulating gloves............... Before first issue and every 6
months thereafter.\1\
Rubber insulating sleeves.............. Before first issue and every 12
months thereafter.\1\
------------------------------------------------------------------------
\1\If the insulating equipment has been electrically tested but not
issued for service, it may not be placed into service unless it has
been electrically tested within the previous 12 months.